The cookie settings on this website are set to 'allow all cookies' to give you the very best experience. Please click Accept Cookies to continue to use the site.

Cummins Automatic Standby Generator Model #GGFD-5573198 #J020429677 LP/NG

$8,499.00
(No reviews yet) Write a Review
Shipping:
Calculated at Checkout
Cummins  Automatic Standby Generator Model #GGFD-5573198  #J020429677 LP/NG

Used Cummins GGFD-5573198 Automatic Standby Generator

Unit Specifications:

Unit Width, in (mm) 40.0 (1016)

Unit Height, in (mm) 50.6 (1285)

Unit Length, in (mm) 82.8 (2103)

Unit Dry Weight, lb (kg) 1567 (711)

Unit Wet Weight, lb (kg) 1637 (743)

Rated Speed, rpm 1800

Voltage Regulation, No Load to Full Load ±1.0%

Random Voltage Variation ±1.0%

Frequency Regulation Isochronous

Random Frequency Variation ±0.6%

Radio Frequency Interference Meets requirements of most industrial and commercial applications

                                                                                   Natural Gas                             Propane          

Cooling                                                              Standby             Prime            Standby             Prime

Fan Load, HP (kW)                                            3.0 (2.2)             3.0 (2.2)         3.0 (2.2)         3.0 (2.2)

Coolant Capacity with radiator, US Gal (L)          7.0 (26.5)          7.0 (26.5)         7.0 (26.0)        7.0 (26.0)

Coolant Flow Rate, Gal/min (L/min)                  20.0 (75.7)       20.0 (75.7)        20.0 (75.7)     20.0 (75.7)

Heat Rejection To Coolant, Btu/min                 1580.0 (1.7)      1440.0 (1.5)     1580.0 (1.7)      1440 (1.5)

Heat Radiated To Room, Btu/min                      790.0 (0.8)        720.0 (0.8)        790.0 (0.8)      720 (0.8)

Maximum Coolant Friction Head, psi                   2.0 (13.8)      2.0 (13.8)              2.0 (13.8)      2 (13.8)

Maximum Coolant Static Head, ft (m)                   10.0 (3.0)     10.0 (3.0)           10.0 (3.0)        10 (3.0)

Air Combustion Air, scfm (m3 /min)                      93.2 (2.6)     85.0 (2.4)            85.5 (2.4)     78.0 (2.2)

Alternator Cooling Air, scfm (m3 /min)                635.0 (18.0)     635.0 (18.0)   635.0 (18.0)        635.0 (18.0)

Radiator Cooling Air, scfm (m3 /min)             4800.0 (135.8)   4800.0 (135.8)    4800.0 (135.8)   4800.0 (135.8)

Max. Static Restriction, in H2O (Pa)              0.50 (124.50)         0.50 (124.50)     0.5 (124.5)        0.5 (124.5)

             MODEL                                                                                       GGFD/GGFE

Engine: Onan modified Ford V-6                                                      ESG-642

Fuel or combination of two fuels                                               Propane (Liquid or Vapor)

                                                                                                          Natural Gas

Fuel flow inlet pressure

Minimum: NG/LPG                                                                       7.0 inch H2O (1.7 kPa)

Maximum:

NG/LP Vapor Withdrawal                                                            13.6 inch H2O (3.4 kPa)

LPG Liquid Withdrawal                                                                     312 PSI (2,153 kPa)

Exhaust:

Connection                                                                                       3 inch NPT

Backpressure (Max Allowed)                                                         30 inch H2O (7.5 kPa)

Electrical System:

Starting Voltage                                                                               12 VDC

Battery Charging Alternator (Max Rating)                                   37 Amps

Cooling System:

Capacity with Standard Radiator                                                   7 Gallons (26.5L)

Lubricating System:

Oil Capacity with Filters

Standby Power (Normal Oil Filter)                                                 6 Qts. (5.7L)

Prime Power (Heavy Duty Oil Filter)                                               9.7 Qts. (9.2L)

Tune Up Specifications:

Spark Plug Gap                                                                                  0.044” (1.1mm)

Battery:

Ground                                                                                                     Negative

Required Battery Voltage                                                                      12 VDC

Group Number                                                                                         31

CCA (Minimum)                                        

   Cold Soak @ 0 Degrees F (-18C)                                                        660

Unit is a Single Phase / Three Phase unit

Unit currently configured for "Single Phase" output

 64.5 HRS on Generator